Updated · by Aurora Star Tech Inc.

Force a defrost with the SPEEDUP pins on a ICP heat pump: With the unit heating and the defrost thermostat closed, shorting the SPEEDUP pins forces a defrost. Outdoor fan stops and strip heat comes on during defrost.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ICP N4H3 heat pumps

How to fix force a defrost with the speedup pins: step by step

  1. Run the unit in heating with the defrost thermostat closed (or jumper the DFT terminals)
  2. Short the SPEEDUP pins with a screwdriver until the reversing valve shifts
  3. Remove the short at once for a brief defrost, or keep it for 2+ seconds to go straight back to heating
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: ICP Heat Pump codes

Models

N4H3

Source: ICP N4H3 Installation Instructions, Defrost System (defrost control board and testing). Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.