Goodman Furnace: Primary (high) limit open, circulator blower runs continuously

Updated · by Aurora Star Tech Inc.

Primary (high) limit open, circulator blower runs continuously on a Goodman furnace: The primary limit circuit is open, so the furnace will not fire, and the circulator blower keeps running to cool the heat exchanger. Before you touch anything, remember the furnace is hot and the blower is live. A limit that opens is a safety doing exactly what it should, so never defeat it. The aim is to find out why the heat exchanger got too hot or why the circuit reads open. Common reasons are airflow, blower speed or a poor connection in the limit wiring.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: 34.5 in chassis gas furnaces

Common causes of primary (high) limit open, circulator blower runs continuously

  • Not enough conditioned air over the heat exchanger
  • Blocked filters, restrictive ductwork, improper circulator blower speed, or failed circulator blower motor
  • Loose or improperly connected wiring in the high limit circuit
  • Closed or blocked supply registers and returns

How to fix primary (high) limit open, circulator blower runs continuously: step by step

  1. Turn power off before any repair or wiring check
  2. Check filters and ductwork for blockage. Clean filters or remove obstructions
  3. Check circulator blower speed and performance. Correct speed or replace the motor if needed
  4. Tighten or correct the wiring connection at the limit
  5. Check the specification sheet for the allowable temperature rise and proper circulator speed
  6. Measure temperature rise after repairs to confirm it is within range
  7. If the limit still opens with good airflow, have a licensed technician test it and check the heat exchanger
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Goodman Furnace codes

Source: Goodman GMVC96 Service and Troubleshooting, p. 60. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.