Goodman Furnace: Poor combustion / flame problems – Goodman/Amana GM9C96
Poor combustion / flame problems - Goodman/Amana GM9C96 on a Goodman furnace: Burner flame is unstable, lifting, yellow or the furnace has repeated flame or pressure switch problems with no single clear code. The manual lists the main venting, drainage and burner factors to check.
Applies to: Goodman/Amana two-stage 96% furnaces GM9C96, GC9C96, AM9C96, AC9C96
Common causes of poor combustion / flame problems - goodman/amana gm9c96
- Venting too long, sagging or with too many tight elbows; flue gas recirculating into the intake
- Furnace holding condensate (bad drain hose connections, dirty trap, wrong slope, A/C coil drain interfering)
- Wrong manifold pressure or orifices for the gas type
- Leaking inducer-to-collector gasket or burr in the collector box orifice
- Burners dirty or misaligned; heat exchanger orifice plate loose or hanging
- Gas line binding the burner assembly
- Not enough combustion air (single-pipe installs) or cabinet air leaks
How to fix poor combustion / flame problems - goodman/amana gm9c96: step by step
- Vent: keep it as short as possible, use 45 degree or long-radius fittings, no sags that trap condensate; if 3 in. pipe is used, transition from 2 in. as close to the furnace as possible; make sure exhaust is not re-entering the intake.
- Drainage: check drain hose connections, clean the condensate trap, confirm the furnace is level end to end with about 3/4 in. tilt toward the front, and that the A/C coil drain is not interfering.
- Set manifold pressure for the gas in use at both low and high fire; if converted to LP, confirm every orifice size.
- Remove the inducer and check the gasket between inducer and collector box cover; check the collector box orifice hole is free of burrs on both sides.
- Check burners are clean, seated and lined up with the heat exchanger tubes, and that the orifice plate between burners and heat exchanger is tight and not missing a screw.
- Make sure the field gas line is not pushing on and distorting the burner assembly.
- Single-pipe installs: confirm the space provides enough combustion air; seal cabinet air leaks that let supply air affect combustion.
- If heat exchanger integrity is in doubt, follow the manufacturer's heat exchanger inspection procedure (Service Bulletin SF-041).
If the unit shows an error code, look it up: Goodman Furnace codes
Models
Goodman/Amana *MVC96 (34.5 in. chassis)
*CVC960403BNB**CVC960603BNB**CVC960804CNB**CVC961005CNB**CVC961205DNB**MVC960403BNB**MVC960603BNB**MVC960803BNB**MVC960804CNB**MVC961005CNB**MVC961005DNB**MVC961205DNB*ACVC96AMVC96GCVC96GMVC96
Goodman/Amana GM9C96/AM9C96
AC9C96AM9C96AM9C960303ANGC9C96GM9C96GM9C960303AN
Goodman/Amana GM9S80/AM9S80
AC9S800403ANAC9S800603ANAC9S800804BNAC9S800805CNAC9S801005CNAM9S800403ANAM9S800603ANAM9S800603BNAM9S800604BNAM9S800803BNAM9S800804BNAM9S800804CNAM9S800805CNAM9S801005CNAM9S801205DNGC9S800403ANGC9S800603ANGC9S800804BNGC9S800805CNGC9S801005CNGM9S800403ANGM9S800603ANGM9S800603BNGM9S800604BNGM9S800803BNGM9S800804BNGM9S800804CNGM9S800805CNGM9S801005CNGM9S801205DN
Goodman/Amana GM9S96/AM9S96
AC9S960403BNAC9S960603BNAC9S960804CNAC9S961005CNAC9S961205CNAC9S961205DNAM9S920403ANAM9S920603BNAM9S920803BNAM9S920804CNAM9S920805CNAM9S921004CNAM9S921005CNAM9S921205DNAM9S960403ANAM9S960603BNAM9S960803BNAM9S960804CNAM9S960805CNAM9S961004CNAM9S961005CNAM9S961205DNGC9S960403BNGC9S960603BNGC9S960804CNGC9S961005CNGC9S961205CNGC9S961205DNGM9S920403ANGM9S920603BNGM9S920803BNGM9S920804CNGM9S920805CNGM9S921004CNGM9S921005CNGM9S921205DNGM9S960403ANGM9S960603BNGM9S960803BNGM9S960804CNGM9S960805CNGM9S961004CNGM9S961005CNGM9S961205DN
Goodman/Amana *MES9 single-stage
ACES96ACES960403BNAAACES960603BNAAACES960804CNAAACES961005CNAAACES961205DNAAAMES92AMES96AMES920403ANAAAMES920603BNAAAMES920803BNAAAMES920804CNAAAMES920805CNAAAMES921004CNAAAMES921005CNAAAMES921205DNAAAMES960403ANAAAMES960603BNAAAMES960803BNAAAMES960804CNAAAMES960805CNAAAMES961005CNAAAMES961205DNAAGCES96GCES960403BNAAGCES960603BNAAGCES960804CNAAGCES961005CNAAGCES961205DNAAGMES92GMES96GMES920403ANAAGMES920603BNAAGMES920803BNAAGMES920804CNAAGMES920805CNAAGMES921004CNAAGMES921005CNAAGMES921205DNAAGMES960403ANAAGMES960603BNAAGMES960803BNAAGMES960804CNAAGMES960805CNAAGMES961005CNAAGMES961205DNAAVCES96VCES960403BNAAVCES960603BNAAVCES960804CNAAVCES961005CNAAVMES96VMES960403ANAAVMES960603BNAAVMES960803BNAAVMES960804CNAAVMES961005CNAA
Goodman/Amana *MVC95/*CVC9 two-stage ComfortNet
GCVC90704CXGCVC90905DXGCVC91155DXGCVC950714CXGCVC950915DXGMVC950453BXGMVC950704CXGMVC950905CXGMVC950905DXGMVC951155DX
Source: Goodman RS6612020r1, Combustion Quality / Venting / Condensate Drainage / Other Causes, p.17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.