Goodman Furnace: No ignition – voltage checks at the ignition control

Updated · by Aurora Star Tech Inc.

No ignition - voltage checks at the ignition control on a Goodman furnace: Step-by-step live checks to find where the sequence stops. Take care, line voltage is present.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: GMES9, GCES9, AMES9, ACES9, VMES9, VCES9 (single stage, 92% and 96%)

Common causes of no ignition - voltage checks at the ignition control

  • No 120 V to the control or door switch open
  • No 24 V from the transformer or thermostat
  • Blown fuse
  • Inducer or igniter circuit not powered

How to fix no ignition - voltage checks at the ignition control: step by step

  1. Measure 120 V at the control between Line 1 (hot) and Line 2 (neutral). None: check the door switch and harness continuity.
  2. Measure 24 V from W to C. None: check the transformer, thermostat and wiring. If the transformer has 24 V but the board shows about 13 V between C and R, check for a blown fuse.
  3. Measure 120 V to the inducer between pin 1 of the 2-pin plug and neutral. None: replace the control.
  4. With the inducer running, measure 120 V to the igniter between pin 2 of the 2-pin plug and neutral during warm-up. None: check the pressure switch.
  5. After warm-up, check for 24 V at the gas valve. It shows for about 7 seconds only if flame is proven.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Goodman Furnace codes

Models

ACES96ACES960403BNAAACES960603BNAAACES960804CNAAACES961005CNAAACES961205DNAAAMES92AMES96AMES920403ANAAAMES920603BNAAAMES920803BNAAAMES920804CNAAAMES920805CNAAAMES921004CNAAAMES921005CNAAAMES921205DNAAAMES960403ANAAAMES960603BNAAAMES960803BNAAAMES960804CNAAAMES960805CNAAAMES961005CNAAAMES961205DNAAGCES96GCES960403BNAAGCES960603BNAAGCES960804CNAAGCES961005CNAAGCES961205DNAAGMES92GMES96GMES920403ANAAGMES920603BNAAGMES920803BNAAGMES920804CNAAGMES920805CNAAGMES921004CNAAGMES921005CNAAGMES921205DNAAGMES960403ANAAGMES960603BNAAGMES960803BNAAGMES960804CNAAGMES960805CNAAGMES961005CNAAGMES961205DNAAVCES96VCES960403BNAAVCES960603BNAAVCES960804CNAAVCES961005CNAAVMES96VMES960403ANAAVMES960603BNAAVMES960803BNAAVMES960804CNAAVMES961005CNAA

Source: Goodman Service and Troubleshooting GMES9*/GCES9*/AMES9*/ACES9*/VMES9*/VCES9* (RS6612016r3) , S-313 Checking Integrated Ignition Control Boards p.45. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.