Goodman Furnace: Heating performance test

Updated · by Aurora Star Tech Inc.

Heating performance test on a Goodman furnace: Before you chase a fault code on a furnace that runs but does not heat well, find out whether it is actually putting out what the rating plate says. A heating performance test does that. The input should be within 5% of the BTU shown on the unit rating plate. Airflow has to land inside the temperature rise range on the spec sheet, and external static pressure should be around 0.5 in water column. Do it on a clean furnace with a clean filter, and you will often find the real problem is gas rate or airflow rather than a bad part.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: All 34.5in chassis gas furnaces

Common causes of heating performance test

  • Gas valve manifold pressure off, so the input is high or low
  • Wrong or partly plugged burner orifices
  • Local gas heating value different from what the furnace was set up for
  • Restricted airflow from a dirty filter or undersized ductwork, throwing off temperature rise
  • External static well above 0.5 in water column

How to fix heating performance test: step by step

  1. Confirm the local natural gas heating value (BTU content) with the utility, since it varies by region
  2. Turn off other gas appliances, then clock the gas meter to find the gas rate in cubic feet per hour
  3. Calculate the BTU input from the gas rate and heating value and compare it to the rating plate. It should be within 5%
  4. Measure supply air and return air temperature at steady state and work out the temperature rise. Compare to the range on the spec sheet
  5. Measure external static pressure (about 0.5 in water column) using the service manual procedure
  6. If input is off, check manifold pressure and orifices before touching anything else. Gas adjustments are for a licensed gas technician
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Goodman Furnace codes

Source: Goodman GMVC96 service and troubleshooting manual, p. 39. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.