Goodman Furnace: Gas valve (two-stage) and front cover pressure switch

Updated · by Aurora Star Tech Inc.

Gas valve (two-stage) and front cover pressure switch on a Goodman furnace: The two-stage valve needs 24V between common and the low fire (main) coil before it will open. The front cover pressure switch sits in series with that low coil, so if that switch is open the valve gets no voltage and acts dead. Many valves get replaced when the real problem is the switch circuit.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: White-Rodgers two-stage gas valve

Common causes of gas valve (two-stage) and front cover pressure switch

  • Front cover pressure switch open, from a blocked or split hose, or a tripped switch
  • No 24V between common and low coil, from wiring or control problem
  • Non-functioning gas valve with 24V present at the coil

How to fix gas valve (two-stage) and front cover pressure switch: step by step

  1. Start with the front cover pressure switch if the valve does not open, because it is in series with the coil
  2. Check the hose to the switch for water, cracks or blockage
  3. Confirm 24V between common and low (main) coil when a heat call is present, because that tells you if the valve is getting what it needs
  4. If 24V is present and the valve stays closed, the valve is the problem
  5. If 24V is absent, trace backwards through the switch and the control
  6. Refer to the gas pressure and pressure switch checks for further testing
  7. Gas valve replacement is licensed gas tech work, so leave it to them
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Goodman Furnace codes

Source: Goodman GMVC96 service manual, p. 50. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.