Goodman Furnace: Dehumidification wiring and logic
Dehumidification wiring and logic on a Goodman furnace: The Dehum input reduces blower speed to 85% during a cooling plus dehum call. The dehumidistat type sets the Dehum logic.
Applies to: Systems with Dehum input
How to fix dehumidification wiring and logic: step by step
- Connect the dehumidistat between R and Dehum if using an external dehumidistat. It must run on 24VAC.
- If the dehumidistat opens on a humidity rise, set Dehum logic to Low using the CoolCloud app or push buttons.
- If the dehumidistat closes on a humidity rise, set Dehum logic to High using the CoolCloud app or push buttons.
- If using a thermostat, set it to energize Dehum only when dehumidification is wanted.
If the unit shows an error code, look it up: Goodman Furnace codes
Source: Goodman GMVC96 service and troubleshooting manual, p. 30-31. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.