Goodman Furnace: Check primary limit control (90% furnaces)

Updated · by Aurora Star Tech Inc.

Check primary limit control (90% furnaces) on a Goodman furnace: The primary limit on these 90% furnaces is the enclosed disk with the colored tab, mounted to see heat exchanger temperature. Most times I get called for a limit, the limit itself is fine and it is doing its job because airflow is bad. Test it with the low voltage wires off. It should read continuous unless the heat exchanger is hotter than the limit setting. A control that is open when stone cold is dead, and a control that opens hot is telling you to go look at the filter and the blower first.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: 90% furnaces, primary limit control

Common causes of check primary limit control (90% furnaces)

  • Heat exchanger temperature above the limit setting (normal open condition when hot)
  • Failed limit control reading open when cold
  • Dirty filter, closed registers or a weak blower pushing the heat exchanger past the setting
  • Loose or corroded connections on the limit terminals that mimic an open

How to fix check primary limit control (90% furnaces): step by step

  1. Shut off power and remove the burner compartment door
  2. Remove the low voltage wires from the limit control terminals so you are testing the switch alone
  3. Test across the two terminals with an ohmmeter. Let the furnace cool fully first
  4. If the reading is not continuous with the unit cold, replace the control
  5. Use the Primary Limit Charts in the technical manual to confirm part number, setting and color code before ordering
  6. Before blaming the limit on a repeat trip, check filter, ductwork and blower speed
  7. Reinstall the burner door, turn power on and verify operation through a full cycle
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Goodman Furnace codes

Source: Goodman GMVC96 service manual, p. 48. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.