Gas Fireplace: Maxitrol GV60 remote valve: fireplace will not light or respond

Updated · by Aurora Star Tech Inc.

Maxitrol GV60 remote valve: fireplace will not light or respond on a gas fireplace: Fireplace with a Maxitrol GV60 battery-powered remote valve: no response, beeping, pilot or burner problems.

Homeowner with a gas fireplace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Fireplaces with Maxitrol GV60 remote valve systems

Common causes of maxitrol gv60 remote valve: fireplace will not light or respond

  • Low or corroded receiver batteries (most common)
  • Remote not communicating
  • Motor or electrical fault
  • Weak thermocouple circuit or valve magnet
  • Vent problem (direct vent)
  • Wrong inlet or manifold pressure

How to fix maxitrol gv60 remote valve: fireplace will not light or respond: step by step

  1. Communication: the remote should show MAN (manual) and a battery icon; pressing flame up/down should turn the valve knob. One beep with no knob movement = electrical problem; one long beep = motor failure; rapid beeps for 3 s = low battery.
  2. Batteries: receiver battery voltage not less than 5.8 VDC. Corrosion in the battery box is the #1 service issue.
  3. Manual light: knob to MAN, press the small tool into the large hole, light the pilot and hold 10 s, then turn back to ON - proves the thermocouple circuit and gas supply.
  4. Thermocouple: red terminal to ground should read 10-15 mV.
  5. Startup: yellow terminal to ground should read 5+ mV when the solenoid clunks in (battery holding the magnet). Red to yellow loss no more than 2-3 mV.
  6. Dropout: shut off gas or blow out the pilot - the red terminal should drop out at about 2 mV; or time it: magnet reset in under 10 s = bad, over 20 s = good.
  7. Direct vent window test: burns right with the glass off but not with it on = vent problem (restrictors are part of the vent).
  8. Gas pressure at full flow: inlet 5-7 in. w.c. NG / 11-14 in. LP; manifold 3.5-4 in. NG / 9.5-10 in. LP (use the rating plate value). Close test ports and leak check.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Heat & Glo Gas Fireplace codes Napoleon Gas Fireplace codes Skytech Gas Fireplace codes

Source: Maxitrol GV60 - 10 technical tests for troubleshooting. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.