Carrier Mini-Split: Remote ON-OFF control on CN23
Remote ON-OFF control on CN23 on a Carrier mini-split: Use the remote ON-OFF input on terminal CN23 with the JR6 jumper removed. Open switch turns the system off and shows CP; closed switch turns it on.
Applies to: Indoor unit controls
How to fix remote on-off control on cn23: step by step
- Remove jumper JR6 before using the ON-OFF function.
- Wire the external switch to CN23.
- Open the switch to turn the system off (display shows CP).
- Close the switch to turn the system on; response is within 2 seconds.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
D5FSOAH06XAKD5FSOAH12XAKD5FSOAH18XAK
More other tips for mini-split
Source: D5FSOA Product Data, p. 15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.