Other: Mini-Split tips (part 4 of 8)
Short, practical technician tips on other for mini-split. Check each one against the manual for your exact model before acting.
Refrigerant removal, purging and recovery
Carrier · D5FSOAH systems using flammable refrigerant
Recover refrigerant safely before any brazing or opening of the circuit. Purging uses oxygen-free nitrogen only.
- Remove refrigerant safely according to local and national rules, or isolate the leaking section with shut-off valves before brazing.
- Evacuate the circuit, then purge it with oxygen-free nitrogen. Repeat as needed.
- Break the vacuum with OFN, fill to working pressure, vent to atmosphere, then pull a vacuum again. Repeat until no refrigerant remains.
- Keep the vacuum pump outlet away from ignition sources and make sure there is ventilation.
- Use recovery cylinders designated for the refrigerant, with a pressure-relief valve and shut-off valves in good order.
- Do not fill recovery cylinders above 80% liquid volume or beyond their maximum working pressure.
- Weigh the cylinder on calibrated scales during recovery. Do not mix refrigerants in units or cylinders.
- Before removing a compressor or oil, evacuate it to an acceptable level. Do not heat the compressor body with an open flame.
Refrigerant system sensor and connection locations
Carrier · D5FSOA indoor unit
Thermistor T1 measures room temperature. Thermistor T2 measures condenser/evaporator temperature (gas). Connections are flared: a gas pipe connection and a liquid pipe connection. A distributor sits in the refrigerant circuit.
Remote battery replacement and life
Carrier · Wireless remote controller
Use two new AAA 1.5V alkaline batteries of the same type. Old or mixed batteries can make the remote malfunction. Batteries last about 6 months. Replace them when the indoor unit no longer beeps or the transmission indicator fails to light. Removing the batteries erases all presets such as Follow Me, which must be set again.
- Slide the back cover off the remote.
- Insert two new AAA alkaline batteries, matching the polarity marks.
- Replace the battery cover.
- If the remote will sit unused for several weeks, remove the batteries to prevent leakage damage.
Remote control battery is low or dead
Carrier · Wireless remote control
If the indoor unit does not beep or the transmission indicator does not light, the batteries need replacing. Average battery life is about 6 months.
- Replace both AAA batteries with new alkaline cells.
Remote control range
Carrier · Wireless remote controller
The remote works up to about 26 ft (8 m) with no obstructions. When the timer function is used, keep the remote within 26 ft (8 m) of the indoor unit.
Remote features not available on this unit
Carrier · Wireless remote RG10L5(2HS)
Some functions are not available on this unit, and some are blocked when matched with a multi-zone condenser.
- Intelligence Sensor and Vertical Swing are not available on this unit.
- When matched with multi-zone condensers, Intelligence Sensor, Humidity Control, ECO, Active Clean, Gear and Silent Mode are not available.
- HEAT mode is not supported on cooling-only units.
Remote ON-OFF control on CN23
Carrier · Indoor unit controls
Use the remote ON-OFF input on terminal CN23 with the JR6 jumper removed. Open switch turns the system off and shows CP; closed switch turns it on.
- Remove jumper JR6 before using the ON-OFF function.
- Wire the external switch to CN23.
- Open the switch to turn the system off (display shows CP).
- Close the switch to turn the system on; response is within 2 seconds.
Remote ON/OFF input (CN23 / JR6)
Carrier · D5FSCAH / D5FLCAH indoor unit
Wiring a remote on/off switch to the indoor unit control board.
- Remove the jumper JR6 to enable ON/OFF control.
- Open contacts on CN23 shut the unit off.
- Closed contacts on CN23 let the unit run.
- When the contacts are open, "CP" shows on the display and wired controller.
- The port provides 12 VDC. Design maximum current is 5 mA.
Remote range, aim and battery life
Carrier · Wireless remote controller
The remote works up to 26 ft (8 m) with no obstructions. A beep confirms each command. Battery life is about 6 months.
- Point the remote toward the right side of the indoor unit when sending commands.
- Keep the remote within 26 ft (8 m) when using the timer.
- Replace batteries when there is no beep from the indoor unit or the transmission indicator does not light.
- Remove batteries if the remote will be unused for several weeks.
Remove the display board (09K/12K/18K)
Carrier · 09K/12K/18K size
Access to the display board after the installing cover is removed.
- Remove the 2 screws and take off the installing cover.
- Remove the display board subassembly.
Remove the drain pump (09K/12K/18K)
Carrier · 09K/12K/18K size
Removes the water pump so the drain line can be freed.
- Pinch the metal wire in the direction shown in the figure to release it.
- Pull out the drain pipe.
- Remove the 2 screws fixing the water pump assembly.
Remove the electrical control box and main control board (09K/12K/18K)
Carrier · 09K/12K/18K size
Anti-static gloves must be worn. Disconnect power before starting.
- Remove the 2 screws holding the electronic control box and the 2 screws of the earth wire.
- Disconnect the temperature sensor, pump, fan motor and water level switch connectors.
- Lift out the electronic control box subassembly.
- Release the 3 clasps of the main control board and remove the 1 earth wire screw.
- Remove the main control board subassembly.
Remove the evaporator (09K/12K/18K)
Carrier · 09K/12K/18K size
Evaporator removal from the indoor unit.
- Remove the 2 screws of the pipe clamp board.
- Remove the 4 screws of the evaporator connecting board and take it off.
- Remove the 1 screw of the evaporator fixing hanger and take the evaporator out.
Remove the fan wheel and fan motor (09K/12K/18K)
Carrier · 09K/12K/18K size
Fan wheel and motor removal for the indoor unit.
- Turn the fan wheel nut anticlockwise, then pull the fan wheel up.
- Remove the 1 screw of the fixing board.
- Turn the three motor nuts anticlockwise.
- Remove the fan motor.
Remove the front panel (continuation of disassembly)
Carrier · Size not stated on page 56
Continuation of the indoor unit panel removal. The size is not named on this page, so confirm it against the disassembly section before you start.
- Disconnect the connectors for the display board and the stepper motor.
- Squeeze the two clasps with your index finger and thumb and lift off the panel.
Remove the ventilation ring and water collector (09K/12K/18K)
Carrier · 09K/12K/18K size
Removes the water collector so the water level switch can be reached. The ion generator is optional and only applies to units that have it.
- Remove the 1 screw of the ventilation ring.
- If fitted, remove the 2 screws of the positive and negative ion generator.
- Remove the 4 screws of the water collector subassembly.
Remove the water level switch from the collector (09K/12K/18K)
Carrier · 09K/12K/18K size
Continuation of the water collector removal.
- Turn the water collector subassembly over.
- Remove the water level switch.
Remove the water pump assembly (09K/12K/18K)
Carrier · 09K/12K/18K size
Final step of the water pump removal, shown on this page.
- Remove the 2 screws fixing the water pump assembly.
Replacing the control board fuse
Carrier · Indoor and outdoor control boards
The control board has an overcurrent fuse. Its rating is printed on the board. Only the blast-proof ceramic type may be used.
- Read the fuse rating printed on the board (examples: T3.15AL/250VAC, T5A/250VAC, T20A/250VAC).
- Fit only a blast-proof ceramic fuse of the same rating.
- Do not use any other fuse type.
SILENCE function reduces performance
Carrier · Indoor unit
The optional SILENCE function lowers operating frequency and can reduce capacity.
- Turn off the SILENCE function if performance is poor.
Silence operation
Carrier · D5FSFAH 9K to 16K
Press SILENCE on the remote to lower the noise level.
- While SILENCE is active the compressor runs below F2 and the indoor unit gives a faint breeze.
Standard protection and comfort features
Carrier · D5CMHA outdoor units, all sizes
The outdoor unit includes a base pan heater as standard on all sizes, a 3-minute time delay for the compressor, and a 46°F heating setback mode.
Stepper motor removal
Carrier · D5FSOAH, sizes 06K to 18K
Remove the panel first. The louver must be opened before the cover comes off.
- Remove the panel.
- Open the louver and push the hooks in the direction shown in the illustration.
- Remove the 2 screws holding the motor cover and take the cover off.
- Remove the 2 screws and take out the stepper motor.
Turbo mode and beeping during error codes
Carrier · D5FS(L)AAH split-type air handler ductless system
When a leak-detection error appears, the unit goes into turbo mode until the code clears. A beeping sound from the unit is normal. For more diagnostic detail, use the Service Manual.
- Leave the unit in turbo mode until the error clears
- Use the Service Manual for further diagnosis
Turn the unit off immediately for these conditions
Carrier · Indoor and outdoor units
Certain conditions are unsafe and need the unit switched off right away.
- Turn off the unit if the power cord is damaged or abnormally warm.
- Turn off the unit if you smell a burning odor.
- Turn off the unit if it makes loud or abnormal sounds.
- Turn off the unit if a power fuse blows or the breaker often trips.
- Turn off the unit if water or other objects fall into or out of it.
- Do not try to fix these issues yourself; contact an authorized service provider.
Unpacking the indoor unit
Carrier · Indoor unit
Remove the carton and packing material without damaging the unit.
- Cut the sealing tape on the carton.
- Remove the sealing nails on the top of the carton.
- Open the carton and remove the middle support plate if fitted.
- Remove the accessory package and any connecting wire.
- Lift the unit out and lay it flat.
- Remove the left and right or upper and lower packaging foam and the packing bag.
Use only approved parts and accessories
Carrier · All D5FSHA service and installation
Non-approved parts can void the warranty and create fire, shock or malfunction risk.
- Use only the included accessories and manufacturer-specified replacement parts.
Vacuum work precautions
Carrier · D5FSOAH06XAK, D5FSOAH12XAK, D5FSOAH18XAK
Always break a vacuum with dry nitrogen. Never use the system compressor as a vacuum pump.
- Break vacuum with dry nitrogen.
- Do not run the compressor to pull vacuum.
Wait before touching electrical parts
Carrier · D5FSHA sizes 6K to 36K
Electrical parts can still carry a charge after power is removed.
- Turn off the power supply before any electrical work.
- Wait at least 10 minutes after power is off before touching electrical components.
Wait for capacitors to discharge before service
Carrier · Indoor and outdoor units
Capacitors keep charge after power is off.
- Turn off and lock out all power.
- Wait 10 minutes after turning off power when connected to a multi-zone outdoor unit.
- Confirm capacitors are discharged before working on the boards.
- Wear anti-static gloves or a wrist strap when handling PCBs.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.