Carrier Mini-Split: Refrigerant removal, purging and recovery
Refrigerant removal, purging and recovery on a Carrier mini-split: Recover refrigerant safely before any brazing or opening of the circuit. Purging uses oxygen-free nitrogen only.
Applies to: D5FSOAH systems using flammable refrigerant
How to fix refrigerant removal, purging and recovery: step by step
- Remove refrigerant safely according to local and national rules, or isolate the leaking section with shut-off valves before brazing.
- Evacuate the circuit, then purge it with oxygen-free nitrogen. Repeat as needed.
- Break the vacuum with OFN, fill to working pressure, vent to atmosphere, then pull a vacuum again. Repeat until no refrigerant remains.
- Keep the vacuum pump outlet away from ignition sources and make sure there is ventilation.
- Use recovery cylinders designated for the refrigerant, with a pressure-relief valve and shut-off valves in good order.
- Do not fill recovery cylinders above 80% liquid volume or beyond their maximum working pressure.
- Weigh the cylinder on calibrated scales during recovery. Do not mix refrigerants in units or cylinders.
- Before removing a compressor or oil, evacuate it to an acceptable level. Do not heat the compressor body with an open flame.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
D5FSOAH06XAKD5FSOAH12XAKD5FSOAH18XAK
More other tips for mini-split
Source: Carrier D5FSOAH service manual, p. 6-7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.