Carrier Mini-Split: Nitrogen leak check
Nitrogen leak check on a Carrier mini-split: Hold the refrigerant piping at the specified pressure for the required time using dry nitrogen, then record the result.
Applies to: D5CURA refrigerant piping
How to fix nitrogen leak check: step by step
- Pressurize the piping with dry nitrogen to 500 psig, not exceeding 550 psi.
- Hold the pressure for at least 30 minutes.
- Record YES or NO on the checklist.
If the unit shows an error code, look it up: Carrier Mini-Split codes
More commissioning tips for mini-split
Source: Carrier D5CURA installation manual, p. 33. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.