Carrier Mini-Split: Field piping pressure test and evacuation limits
Field piping pressure test and evacuation limits on a Carrier mini-split: Field refrigerant piping must be pressure tested with inert gas, then vacuum tested, before charging. Indoor field joints also need a tightness test.
Applies to: Field refrigerant piping of D5FSOAH systems
How to fix field piping pressure test and evacuation limits: step by step
- Pressure test field piping with inert gas. The low side is tested to its design pressure. The high side is tested to its design pressure, unless it cannot be isolated from the low side; then test the whole system to the low side design pressure.
- Hold the test pressure for at least 1 hour with no drop on the gauge. Gauge resolution must not exceed 5% of test pressure.
- Evacuate to the vacuum level given in the manual or lower. The lower of 500 microns or the local code value applies.
- Isolate the pump and check that pressure does not rise above 1500 microns within 10 minutes.
- Test indoor field-made joints with a detector sensitive to 5 g/year of refrigerant or better, at at least 0.25 times the maximum allowable pressure. No leak is allowed.
- Do not bury more than 36 in. (914 mm) of refrigerant pipe. If any section is buried, provide a 6 in. (152 mm) vertical rise to the outdoor unit valve connections.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
D5FSOAH06XAKD5FSOAH12XAKD5FSOAH18XAK
More commissioning tips for mini-split
Source: Carrier D5FSOAH service manual, p. 1, p. 5. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.