Carrier Heat Pump: Scenario 2 (default): wired controller with RS485 communication
Scenario 2 (default): wired controller with RS485 communication on a Carrier heat pump: Default method. Uses the KSACN1401AAA wired controller with RS485 between indoor and outdoor units, so the system is fully communicating.
Applies to: D5CURA with KSACN1401AAA wired controller
How to fix scenario 2 (default): wired controller with rs485 communication: step by step
- Use 16 AWG stranded shielded cable for RS485 communication.
- Wire the indoor/outdoor units and wired controller as shown in Fig. 12.
- Set SW1-4 at the air handler as shown in Fig. 13.
- Do not use any 24V terminal at the air handler or outdoor unit in this scenario.
- Use 24V communication only for emergency operation, service or troubleshooting; it is not a standard method.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK
Source: D5CURA product data, p. 118. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.