Carrier Heat Pump: Scenario 1: 24V thermostat with RS485 communication wiring
Scenario 1: 24V thermostat with RS485 communication wiring on a Carrier heat pump: Preferred method. Lets a 24V thermostat work with RS485 communication between the indoor and outdoor units. No 24V terminal at the outdoor unit can be used in this scenario.
Applies to: D5CURA with 24V thermostat and compatible indoor unit
How to fix scenario 1: 24v thermostat with rs485 communication wiring: step by step
- Use 16 AWG stranded shielded cable for RS485 between indoor and outdoor units.
- Do not use the B terminal and W terminal together at the air handler.
- Use W only with a conventional thermostat for the heat demand at the air handler.
- Leave DS unused; it is a reserve terminal.
- Set the indoor unit dip switches for Scenario 1 as shown in the manual (Fig. 11).
- Never connect 24V AC to S1 - S2; this damages the system.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK
Source: D5CURA product data, p. 117. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.