Carrier Heat Pump: Refrigerant removal and evacuation for flammable systems
Refrigerant removal and evacuation for flammable systems on a Carrier heat pump: Follow this order when breaking into the refrigerant circuit for repair or other work.
Applies to: Flammable refrigerant service
How to fix refrigerant removal and evacuation for flammable systems: step by step
- Safely remove refrigerant per local and national rules, recovering into correct cylinders if venting is not allowed.
- Evacuate the circuit.
- Purge with oxygen-free nitrogen; do not use compressed air or oxygen.
- Repeat the nitrogen purge until no refrigerant remains.
- Vent the system to atmospheric pressure before working on it.
- Keep the vacuum pump outlet away from ignition sources and make sure there is ventilation.
- When using flame to open the circuit, flush or purge continuously with inert gas.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
37MUHA37MURAD5FUAAH18AAKD5FUAAH24AAKD5FUAAH30AAKD5FUAAH36AAKD5FUAAH48AAKD5FUAAH60AAK
Source: D5FUAA Service Manual, p. 6. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.