Carrier Heat Pump: Refrigerant line length and insulation
Refrigerant line length and insulation on a Carrier heat pump: Minimum line length between indoor and outdoor units is 10 ft (3 m). Insulate each refrigerant line separately with at least 1/2 in (12.7 mm) thick insulation. Closed-cell insulation is recommended for long-line runs. Isolate the tubing from the building structure so vibration and noise do not transmit into it. Long-line applications need no change in line sizing.
Applies to: D5CMHA line sets
How to fix refrigerant line length and insulation: step by step
- Keep the line run at least 10 ft (3 m).
- Insulate the liquid and suction lines separately, at least 1/2 in (12.7 mm) thick.
- Use closed-cell insulation on long-line runs.
- Isolate the tubing from the structure.
If the unit shows an error code, look it up: Carrier Heat Pump codes
More commissioning tips for heat pump
Source: D5CMHA Product Data, p. 124. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.