Carrier Heat Pump: Joint leak test

Updated · by Aurora Star Tech Inc.

Joint leak test on a Carrier heat pump: Field-made joints must be leak tested with a detector sensitive to 1/8 oz (5 g) per year of refrigerant or better.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Field refrigerant joints

How to fix joint leak test: step by step

  1. Use a detector rated to 1/8 oz (5 g) per year or better.
  2. Test joints at standstill and under operation.
  3. Test indoor field-made joints at 125% of maximum allowable pressure. No leak is allowed.
  4. Use leak detection fluids without chlorine-based detergents.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Heat Pump codes

Models

D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK

Source: D5CURA installation manual, p. 4. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.