Carrier Heat Pump: Force defrost with the outdoor SW4 button
Force defrost with the outdoor SW4 button on a Carrier heat pump: Forced defrost is only for testing defrost. Defrost termination conditions still set how long it runs.
Applies to: Outdoor unit
How to fix force defrost with the outdoor sw4 button: step by step
- Press and hold the outdoor SW4 button for 10 seconds.
- Do not use SW3 for forced defrost; it is not active.
- Watch the defrost termination conditions, which still limit the run time.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK
More service & test modes tips for heat pump
Source: D5CURA installation manual, p. 28. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.