Carrier Heat Pump: Evaporator coil temperature protection in heating
Evaporator coil temperature protection in heating on a Carrier heat pump: In heating, the indoor coil protection limits a temperature offset (ΔTE1) based on room temperature T1.
Applies to: D5FSAA heat pump units
Common causes of evaporator coil temperature protection in heating
- Room temperature T1 at or above 66°F (19°C) gives ΔTE1 = 0.
- Room temperature T1 from 59°F (15°C) to below 66°F (19°C) gives ΔTE1 = 66°F minus T1.
- Room temperature T1 below 59°F (15°C) gives ΔTE1 = 7.2°F (4°C).
How to fix evaporator coil temperature protection in heating: step by step
- Measure room temperature T1 at the indoor unit.
- Apply the ΔTE1 value from the table to judge the coil protection limit.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Source: Carrier D5FSAA product data, p. 3. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.