Carrier Heat Pump: Evacuation test
Evacuation test on a Carrier heat pump: Check that the system holds vacuum after isolation from the pump.
Applies to: Split system field piping
How to fix evacuation test: step by step
- Pull the system to the vacuum level specified in the manual.
- Isolate the system from the vacuum pump.
- Confirm pressure does not rise more than 1/2 inch within 10 minutes.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK
Source: D5CURA installation manual, p. 4. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.