Carrier Heat Pump: Evacuate using the triple evacuation method

Updated · by Aurora Star Tech Inc.

Evacuate using the triple evacuation method on a Carrier heat pump: Use only if the vacuum pump cannot reach 1/4 inch and the system has no liquid water.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Refrigerant lines and indoor coil

How to fix evacuate using the triple evacuation method: step by step

  1. Attach gauges and evacuate the system to 28 inches of mercury. Run the pump 15 minutes more.
  2. Close the service valves and shut off the pump.
  3. Connect a nitrogen cylinder and regulator. Flow nitrogen until system pressure is 2 psig.
  4. Close the service valve and let the system stand for 1 hour.
  5. Repeat the evacuation and nitrogen steps as shown in Fig. 35.
  6. Confirm the system holds a deep vacuum to show it is tight and dry.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Heat Pump codes

Models

D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK

Source: D5CURA installation manual, p. 30. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.