Carrier Heat Pump: DC fan motor check (indoor and outdoor)
DC fan motor check (indoor and outdoor) on a Carrier heat pump: Check the fan motor supply and control signals. Indoor DC fan motors have the control chip in the motor. Outdoor DC fan motors have the control chip in the outdoor PCB.
Applies to: D5FUHA
Common causes of dc fan motor check (indoor and outdoor)
- Faulty fan motor
- Faulty fan motor control chip or PCB
How to fix dc fan motor check (indoor and outdoor): step by step
- Indoor fan: with power on and unit in standby, measure the voltage between pin 1 and pin 3, and between pin 4 and pin 3 at the fan motor connector.
- Indoor fan: if the voltage is not in the range in the pin table, replace the PCB.
- Outdoor fan: shut off power and release the UVW connector.
- Outdoor fan: measure the resistance of U-V, U-W and V-W.
- Outdoor fan: if the three resistances are not equal, replace the fan motor.
- Outdoor fan: if they are equal, replace the PCB.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Source: D5FUHA service manual, p. 26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.