Carrier Heat Pump: Air handler (AHU) limits and added charge
Air handler (AHU) limits and added charge on a Carrier heat pump: A maximum of two AHUs can be added to an MZ system. When two AHUs are connected to any MZ outdoor unit, no other indoor units can be added. If a 30K or 36K AHU is connected to any outdoor unit, add 500 g (17.6 oz) of refrigerant. 30K and 36K indoor units are not compatible with phased-out models.
Applies to: D5CMHA multi-zone systems with AHUs
How to fix air handler (ahu) limits and added charge: step by step
- Limit the system to two AHUs maximum.
- With two AHUs installed, do not add other indoor units.
- For any 30K or 36K AHU, add 500 g (17.6 oz) of refrigerant charge.
If the unit shows an error code, look it up: Carrier Heat Pump codes
More commissioning tips for heat pump
Source: D5CMHA Product Data, p. 124. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.