Carrier Heat Pump: Adding charge on long line sets
Adding charge on long line sets on a Carrier heat pump: The outdoor unit is shipped with a full R-454B charge that covers about 25 ft of line. Longer runs need extra refrigerant up to the allowed length.
Applies to: D5CURA all sizes
How to fix adding charge on long line sets: step by step
- Check the total line length against the 24.6 ft (7.5 m) standard piping length.
- For runs over the standard length, add 0.7 oz/ft (65 g/m) of extra line.
- Do not exceed the maximum total piping length and drop height for the size (see the line-length table).
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK
More commissioning tips for heat pump
Source: D5CURA service manual, p. 20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.