Carrier Heat Pump: 4-way valve check
4-way valve check on a Carrier heat pump: Check the 4-way reversing valve coil voltage and resistance.
Applies to: D5CURA outdoor unit 4-way valve
Common causes of 4-way valve check
- Wrong coil voltage for the operating mode
- Faulty valve coil
How to fix 4-way valve check: step by step
- Power on and measure the coil voltage with a digital tester.
- In cooling the voltage should be 0 V; in heating it should be about equal to the supply voltage.
- If the voltage is outside this range, the PCB is faulty and must be replaced.
- Turn off the power and measure the coil resistance; it should be 1.8 to 2.5 kΩ.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK
Source: D5CURA service manual, p. 64. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.