Carrier Air Handler: Secondary condensate pan and overflow protection

Updated · by Aurora Star Tech Inc.

Secondary condensate pan and overflow protection on a Carrier air handler: Where water damage could occur from overflow, a secondary pan or drain line is required.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: D5FULA installs in or above living space

How to fix secondary condensate pan and overflow protection: step by step

  1. Install a field-supplied external condensate pan under the whole unit and run a secondary drain line with a trap into it.
  2. Drain the external pan to a visible location.
  3. Alternatively, where local code permits, run a separate 3/4 in condensate line with a trap to a visible location.
  4. Install a float switch to shut the unit off if the secondary pan fills.
  5. Tell the owner that the unit needs service if water runs from the secondary drain or pan.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Air Handler codes

Source: Carrier D5FULA installation instructions, p. 24. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Air Handler Emergency

647-657-2977