Carrier Air Handler: Rotate evaporator and reconnect sensors
Rotate evaporator and reconnect sensors on a Carrier air handler: Used when the unit is set up for vertical downflow. Route wires through the cabinet correctly and reseal the openings.
Applies to: D5FSAA / D5FLAA air handler, vertical downflow
How to fix rotate evaporator and reconnect sensors: step by step
- Remove the evaporator and drain pan, then rotate them 180 degrees for vertical down.
- Adjust the mounting part positions for the unit direction.
- Reinstall the evaporator and drain pan.
- Reconnect the T1, T2, T2A and T2B sensor plugs and the electronic expansion valve (EEV), then tie up the sensor wires.
- Cut the foam gasket and remove the knockouts.
- Hook the wire into the strap and run it down through the wire slot.
- Put the foam gasket back over the wires.
If the unit shows an error code, look it up: Carrier Air Handler codes
Source: Carrier D5FSAA/D5FLAA installation manual, p. 21. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.