Carrier Air Handler: Refrigerant piping leak check

Updated · by Aurora Star Tech Inc.

Refrigerant piping leak check on a Carrier air handler: The system is pressure-tested before evacuation. Use dry nitrogen only.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: D5FSAA / D5FLAA ductless air handler system

How to fix refrigerant piping leak check: step by step

  1. Pressurise the system to 500 psig, with a maximum of 550 psi.
  2. Hold the pressure for at least 30 minutes using dry nitrogen.
  3. Never use air or oxygen-containing gases for this test.
  4. Record YES or NO on the start-up checklist.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Air Handler codes

More commissioning tips for air handler

Source: Carrier D5FSAA and D5FLAA installation manual, p. 50. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.