Carrier Air Handler: Refrigerant pipe burial limits
Refrigerant pipe burial limits on a Carrier air handler: Do not bury more than 36 in (914 mm) of refrigerant pipe. If any pipe is buried, there must be a 6 in (152 mm) vertical rise to the outdoor unit valve connections. Too much buried pipe lets refrigerant migrate during shutdown and can slug the compressor at start-up.
Applies to: D5FUAA system piping
How to fix refrigerant pipe burial limits: step by step
- Keep buried refrigerant pipe to 36 in (914 mm) or less.
- If any pipe is buried, provide a 6 in (152 mm) vertical rise to the outdoor valve connections.
If the unit shows an error code, look it up: Carrier Air Handler codes
Models
45MUAAQ18XX345MUAAQ24XX345MUAAQ30XX345MUAAQ36XX345MUAAQ48XX345MUAAQ60XX3D5FUAA
More commissioning tips for air handler
Source: Carrier D5FUAA crossover air handler product data, p. 2. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.