Carrier Air Handler: Refrigerant leak sensor wiring and secondary input
Refrigerant leak sensor wiring and secondary input on a Carrier air handler: The leak sensor connects to the primary leak mitigation input at CN8 on the interface board. A secondary input at CN5 is available but must be enabled with DIP switch SW5.
Applies to: D5FULA with R454B leak mitigation kit
How to fix refrigerant leak sensor wiring and secondary input: step by step
- Connect the refrigerant sensor wire to CN8 (primary, active by default).
- To use the secondary input at CN5, turn on DIP switch SW5.
- Follow the wiring diagram and the leak mitigation kit label for operating details.
If the unit shows an error code, look it up: Carrier Air Handler codes
More commissioning tips for air handler
Source: Carrier D5FULA installation instructions, p. 22. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.