Carrier Air Handler: Refrigerant leak sensor (flammable refrigerant units)
Refrigerant leak sensor (flammable refrigerant units) on a Carrier air handler: Units fitted with a refrigerant sensor shut down the outdoor compressor on a leak and run the indoor fan. The sensor has a 15 year service life and cannot be repaired.
Applies to: D5FUHAQ indoor units with refrigerant sensor
Common causes of refrigerant leak sensor (flammable refrigerant units)
- Refrigerant sensor detects leaked flammable refrigerant
- Sensor has reached end of service life or is faulty (display shows FHCC)
How to fix refrigerant leak sensor (flammable refrigerant units): step by step
- Keep the unit powered, except during service, so the leak detection system stays active.
- If the indoor unit buzzes and shows a leak code, treat it as a refrigerant leak and find the source before restarting.
- Confirm the outdoor compressor is stopped and the indoor fan is running as expected for a leak event.
- If the display shows FHCC, the sensor is faulty.
- Replace the sensor only with the manufacturer-specified sensor. Do not repair it.
If the unit shows an error code, look it up: Carrier Air Handler codes
Source: D5FUHAQ Owner's Manual, p. 4. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.