Carrier Air Handler: Refrigerant leak detected by the leak detection system
Refrigerant leak detected by the leak detection system on a Carrier air handler: Response of the unit when the refrigerant sensor detects a leak. The manual does not list the leak alarm code shown on the display.
Applies to: D5FULA crossover evaporator coil with flammable refrigerant and refrigerant sensor
How to fix refrigerant leak detected by the leak detection system: step by step
- Expect the indoor unit to show an error code and buzz.
- Expect the outdoor compressor to stop immediately and the indoor fan to run.
- Keep the unit powered, except during service, so the leak detection system works.
- Ventilate the area before breaking into the system or doing any hot work.
- Remove or extinguish all open flames and ignition sources.
- Check the area with a leak detector suitable for flammable refrigerants.
- If a leak needs brazing, recover all refrigerant or isolate the leaking section with shut-off valves first.
If the unit shows an error code, look it up: Carrier Air Handler codes
Source: D5FULA installation instructions, p. 5-6. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.