Carrier Air Handler: Pressure, vacuum and leak test limits for field piping
Pressure, vacuum and leak test limits for field piping on a Carrier air handler: Limits for testing field refrigerant piping on split systems.
Applies to: Field piping on D5FUAAH split systems
How to fix pressure, vacuum and leak test limits for field piping: step by step
- Pressure test field piping with inert gas. Hold the test pressure for at least 1 hour with no drop on the gauge. Gauge resolution must not exceed 5% of the test pressure.
- After evacuation, isolate the pump. Pressure must not rise above 1500 microns within 10 minutes. Vacuum must reach 500 microns or lower, or the level required by local code.
- Test field-made indoor joints at at least 125% of the maximum allowable pressure. Sensitivity must be 1/8 oz (5 g) per year or better. No leak is allowed.
If the unit shows an error code, look it up: Carrier Air Handler codes
More commissioning tips for air handler
Source: D5FUAAH Owner's Manual, p. 4. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.