Carrier Air Handler: Leak detection on flammable refrigerant joints

Updated · by Aurora Star Tech Inc.

Leak detection on flammable refrigerant joints on a Carrier air handler: Methods allowed for finding refrigerant leaks on A2L flammable refrigerant systems.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: D5FUHAQ refrigerant circuit

How to fix leak detection on flammable refrigerant joints: step by step

  1. Test joints with leak detection equipment rated at 1/8 oz (5 g) per year or better, with the system at standstill and under operation.
  2. Never use a flame or halide torch to find a leak.
  3. Use only leak detectors suitable for flammable refrigerant. Calibrate them in a refrigerant-free area and set them to no more than 25% of LFL.
  4. Bubble or fluorescent leak detection fluids are acceptable.
  5. If a leak needs brazing, first recover the refrigerant or isolate that section with shut-off valves.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Air Handler codes

Source: D5FUHAQ Owner's Manual, p. 5. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.