Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Carrier Air Handler: Installation direction options

Updated · by Aurora Star Tech Inc.

Installation direction options on a Carrier air handler: The unit can be installed vertical (down flow and up flow) or horizontal (right flow and left flow). For horizontal installs a secondary drain pan is required. Vertical up and horizontal left do not require changing the evaporator direction. A minimum 5 in (127 mm) dimension is shown on the figure.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: D5FUHA indoor unit

How to fix installation direction options: step by step

  1. Select vertical down, vertical up, horizontal right or horizontal left.
  2. Change the evaporator direction only for vertical down and horizontal right installs.
  3. Install a secondary drain pan for horizontal installs.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Air Handler codes

Models

D5FUHAH24AAKD5FUHAH36AAKD5FUHAH60AAKEHKMD05KNEHKMD08KNEHKMD10KNEHKMD15KNEHKMD20KNEHKMD25KN

Source: D5FUHA installation manual, p. 19. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Air Handler Emergency

647-657-2977