Carrier Air Handler: Indoor unit field wiring
Indoor unit field wiring on a Carrier air handler: Base unit wiring only. Confirm supply voltage, frequency, phase and ampacity against the rating plate before connecting.
Applies to: D5FUAA indoor unit
How to fix indoor unit field wiring: step by step
- Strip signal cable ends to about 1/2 in (12 mm) and strip the wire ends.
- Crimp fork terminals to the wire ends.
- Open the front panel and remove the electric control box cover.
- Thread the power and signal cables through the wire outlet.
- Match wire colors and labels to the terminal block.
- Screw each fork terminal firmly to its matching terminal, using the serial number and wiring diagram on the control box cover.
- Clamp the cable so it is not loose and does not strain the fork terminals.
- Reattach the electric box cover.
- Use copper wire only and size wires per NEC and local codes.
- Keep the interconnection cable away from copper tubing; the refrigerant circuit can get very hot.
- Lock out and tag the main disconnect before service. Line-side field wires in the fan coil stay live when the pull-out is removed.
- Auxiliary electric heater needs a separate power supply; do not power it from the outdoor unit.
If the unit shows an error code, look it up: Carrier Air Handler codes
Models
45MUAAQ18XX345MUAAQ24XX345MUAAQ30XX345MUAAQ36XX345MUAAQ48XX345MUAAQ60XX3D5FUAA
Source: D5FUAA service manual, p. 13. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.