Carrier Air Handler: Horizontal installation needs a secondary drain pan
Horizontal installation needs a secondary drain pan on a Carrier air handler: Multi-poise unit can be set vertical up, horizontal left or right, or upflow/downflow. Horizontal installs need a secondary drain pan (not supplied) with at least 5 in (127 mm) between the bottom of the air handler and the pan for drainage. Vertical up and horizontal left do not require changing the evaporator direction.
Applies to: D5FUAA air handler
How to fix horizontal installation needs a secondary drain pan: step by step
- Confirm the install orientation from the multi-poise drawings.
- For horizontal installs, fit a secondary drain pan not supplied with the unit.
- Keep at least 5 in (127 mm) between the air handler bottom and the secondary pan.
If the unit shows an error code, look it up: Carrier Air Handler codes
Models
45MUAAQ18XX345MUAAQ24XX345MUAAQ30XX345MUAAQ36XX345MUAAQ48XX345MUAAQ60XX3D5FUAA
More commissioning tips for air handler
Source: Carrier D5FUAA crossover air handler product data, p. 4. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.