Carrier Air Handler: Forced operation modes from the wired controller
Forced operation modes from the wired controller on a Carrier air handler: The wired controller's black button (KEY1) steps the unit through forced modes. Use this for commissioning or service checks, not for normal operation.
Applies to: Wired controller only
How to fix forced operation modes from the wired controller: step by step
- Press KEY1 once to enter forced automatic mode.
- Press KEY1 again to enter forced cooling mode. The display shows FC.
- Press KEY1 again to shut the unit down.
- While in forced cooling (display FC), press and hold KEY1 for 5 seconds to enter forced defrost mode.
If the unit shows an error code, look it up: Carrier Air Handler codes
Models
D5FUHAH24AAKD5FUHAH36AAKD5FUHAH60AAKEHKMD05KNEHKMD08KNEHKMD10KNEHKMD15KNEHKMD20KNEHKMD25KN
More service & test modes tips for air handler
Source: Carrier D5FUHA installation instructions, p. 43. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.