Carrier Air Handler: Flare refrigerant pipe ends
Flare refrigerant pipe ends on a Carrier air handler: A correct flare is needed for an air-tight seal. Once flared, the nut cannot be fitted or turned around.
Applies to: D5FSAA / D5FLAA air handler, copper line set
How to fix flare refrigerant pipe ends: step by step
- Seal the pipe ends with PVC tape after deburring to keep debris out.
- Sheath the pipe with insulation.
- Put the flare nuts on both ends first and check they face the correct direction.
- Remove the PVC tape only when you are ready to flare.
- Clamp the flare block on the pipe end so the pipe extends past the flare form.
- Place the flaring tool on the form and turn the handle clockwise until the pipe is fully flared to the Table 14 dimensions.
- Remove the flaring tool and block, then check the flare for cracks and an even flare.
If the unit shows an error code, look it up: Carrier Air Handler codes
Source: Carrier D5FSAA/D5FLAA installation manual, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.