Carrier Air Handler: Flare refrigerant line connections

Updated · by Aurora Star Tech Inc.

Flare refrigerant line connections on a Carrier air handler: Procedure for cutting, deburring, flaring and tightening the copper refrigerant lines at the indoor unit. Flare nuts must be placed on the pipe before flaring because they cannot be fitted after the flare is made.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: D5FUHA indoor unit, 3/8 in liquid and 3/4 in gas lines

Common causes of flare refrigerant line connections

  • Burrs or an oblique cut can break the air-tight seal
  • Over-tightening can damage the bell mouth and under-tightening leaks

How to fix flare refrigerant line connections: step by step

  1. Measure the distance between the indoor and outdoor units and cut the pipe slightly longer, square to 90 degrees.
  2. Remove all burrs with a reamer or deburring tool while holding the pipe pointing down.
  3. Seal the pipe ends with PVC tape until flaring.
  4. Place the flare nuts on both ends facing the correct direction.
  5. Clamp the flare block so the pipe end extends past the form, then flare to the dimensions in the flare table.
  6. Inspect the flare for cracks and even shape.
  7. Connect the low-pressure (gas) line first on the outdoor side, then the high-pressure line; connect outdoor pipes first, then indoor.
  8. Apply a thin coat of refrigeration oil to the flared ends.
  9. Align the centers of the two pipes and tighten the nut by hand.
  10. Hold the unit fitting with a backup wrench and tighten with a torque wrench to the value in the torque table.
  11. Use a backup wrench on both connecting and disconnecting.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Air Handler codes

Models

D5FUHAH24AAKD5FUHAH36AAKD5FUHAH60AAKEHKMD05KNEHKMD08KNEHKMD10KNEHKMD15KNEHKMD20KNEHKMD25KN

Source: D5FUHA installation instruction, p. 27-28. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.