Applies to: Indoor and outdoor units using flammable refrigerant

How to fix flammable refrigerant work: area checks before opening the system: step by step

  1. Check the area with an appropriate refrigerant detector before and during work.
  2. Use leak detection equipment suitable for flammable refrigerants (no sparking, sealed or intrinsically safe).
  3. Have a dry powder or CO2 fire extinguisher next to the charging area if any hot work is done.
  4. Survey the area for ignition sources. Keep smoking and open flames well away, and post 'No Smoking' signs.
  5. Make sure the area is open or well ventilated before breaking into the system or doing hot work, and keep ventilation running during the work.
  6. Check that refrigerant-containing parts are installed where corrosion is unlikely.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Air Handler codes

Source: Carrier D5FSAAH / D5FLAAH installation manual, p. 8. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.