Carrier Air Handler: Evacuation acceptance limit
Evacuation acceptance limit on a Carrier air handler: After reaching the specified vacuum, isolate the pump. The pressure must not rise above 1500 microns within 10 minutes. The target vacuum is the lesser of 500 microns or the value required by national and local codes.
Applies to: Field refrigerant piping evacuation
How to fix evacuation acceptance limit: step by step
- Pull the system to the specified vacuum, no higher than 500 microns or the code value if lower.
- Isolate the system from the vacuum pump.
- Watch the gauge for 10 minutes; the pressure must stay at or below 1500 microns.
If the unit shows an error code, look it up: Carrier Air Handler codes
Models
D5FUHAH24AAKD5FUHAH36AAKD5FUHAH60AAKEHKMD05KNEHKMD08KNEHKMD10KNEHKMD15KNEHKMD20KNEHKMD25KN
More commissioning tips for air handler
Source: Carrier D5FUHA service manual, p. 5. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.