Carrier Air Handler: DIP switch and connector notes for wiring
DIP switch and connector notes for wiring on a Carrier air handler: Remove the short connector on JR1 when using the ON-OFF function. Remove the short connector on J7 when using the water level switch function. Other DIP switches default to OFF. Refer to the Installation Manual for DIP switch functions. On CN23/CN33, connect wires to the left and right terminals, not the middle ones.
Applies to: D5FS(L)AAH wiring diagrams 18K to 60K
How to fix dip switch and connector notes for wiring: step by step
- Remove the short connector on JR1 only if the ON-OFF function is used.
- Remove the short connector on J7 only if the water level switch is used.
- Connect CN23/CN33 wires to the outer terminals only.
If the unit shows an error code, look it up: Carrier Air Handler codes
More commissioning tips for air handler
Source: D5FS(L)AAH Owner's Manual, p. 19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.