Carrier Air Handler: Decommissioning and refrigerant recovery
Decommissioning and refrigerant recovery on a Carrier air handler: Steps for recovering refrigerant and decommissioning a flammable refrigerant unit.
Applies to: D5FUHAQ units being serviced or retired
How to fix decommissioning and refrigerant recovery: step by step
- Make sure the technician knows the equipment, and take an oil and refrigerant sample if analysis may be needed.
- Isolate the system electrically and make sure power is available.
- Pump the system down if possible. If not, use a manifold to recover from several points.
- Place the cylinder on scales before recovery.
- Run the recovery machine per its instructions.
- Do not fill cylinders above 80% of volume as liquid, and never exceed the cylinder maximum working pressure.
- Evacuate compressors or compressor oil to an acceptable level before removing them. Do not heat the compressor body with an open flame.
- Do not reuse recovered refrigerant in another system unless it is cleaned and checked.
- Label the equipment as decommissioned and emptied, with date and signature, and keep the flammable refrigerant label on it.
If the unit shows an error code, look it up: Carrier Air Handler codes
Source: D5FUHAQ Owner's Manual, p. 6. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.