Carrier Air Handler: Convert the air handler from 230 V to 115 V supply
Convert the air handler from 230 V to 115 V supply on a Carrier air handler: Field change of the motor plug and the 24 V transformer connection. Start from the factory 230 V default.
Applies to: D5FUAA sizes 18K to 60K, 115 V power supply
How to fix convert the air handler from 230 v to 115 v supply: step by step
- Unplug the white 230 V connector from the fan motor wire. Connect the red 115 V connector to the fan motor wire.
- Unplug these connectors from the main control board: CN11 (power wire), CN15 and CN34 (fan motor), CN22 (EEV), CN26 (refrigerant sensor), CN46 (T1 sensor), CN47 (T2 sensor), and CN7 (T2A and T2B sensors).
- Remove the two screws holding the control box and pull the control box out of the cabinet.
- Unplug the default 230 V connection wire (red connector) from the 24 V transformer and from port CN12 on the main control board.
- Install the 115 V connection wire: connect its white connector to the 24 V transformer and its other connector to CN12 on the main control board.
- Reinstall the control box in the cabinet, fix it with screws, and seat the wire body properly.
- Reconnect the temperature sensors T1, T2, T2A and T2B, the refrigerant detection sensor, the EEV, and the fan motor power pair plug (CN11).
- Reconnect all other connectors removed in step 2.
If the unit shows an error code, look it up: Carrier Air Handler codes
Models
45MUAAQ18XX345MUAAQ24XX345MUAAQ30XX345MUAAQ36XX345MUAAQ48XX345MUAAQ60XX3D5FUAA
Source: D5FUAA installation instructions, p. 20-22. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.