Carrier Air Handler: Braze connections and nitrogen pressure test

Updated · by Aurora Star Tech Inc.

Braze connections and nitrogen pressure test on a Carrier air handler: When the air handler connection is brazed, flow nitrogen through the system while brazing, then pressure test. Insulate the suction line completely, including the outdoor unit valves. A flare-to-braze adapter may be used at the air handler.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: D5FUHA line set brazing

Common causes of braze connections and nitrogen pressure test

  • Brazing without nitrogen flow can leave oxidation inside the line set

How to fix braze connections and nitrogen pressure test: step by step

  1. Cut and deburr the tubing to the outside diameters in the connection table.
  2. Set up the nitrogen apparatus and connect it to the outdoor unit so nitrogen flows while brazing.
  3. Braze the tubing and any fittings to get a proper seal.
  4. Pressurize the system with nitrogen and pressure test to a maximum of 500 psig for at least 60 minutes.
  5. Insulate the suction line completely, including the outdoor unit valves.
  6. If a flare-to-braze adapter is used, repeat the same cut, braze and test steps at the adapter.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Air Handler codes

Models

D5FUHAH24AAKD5FUHAH36AAKD5FUHAH60AAKEHKMD05KNEHKMD08KNEHKMD10KNEHKMD15KNEHKMD20KNEHKMD25KN

Source: D5FUHA installation instruction, p. 29. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.