Carrier Air Handler: Air evacuation of the refrigerant circuit

Updated · by Aurora Star Tech Inc.

Air evacuation of the refrigerant circuit on a Carrier air handler: Evacuate the circuit on first install and whenever the unit is relocated. Air and moisture raise pressure, lower efficiency and can damage the unit. Check that the refrigerant pipes between indoor and outdoor units and all wiring are connected correctly before starting.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: D5FUHA crossover air handler, sizes 18K to 60K

How to fix air evacuation of the refrigerant circuit: step by step

  1. Connect the manifold gauge charge hose to the service port on the outdoor unit's low pressure valve.
  2. Connect a second charge hose from the manifold gauge to the vacuum pump.
  3. Open the low pressure side of the gauge and keep the high pressure side closed.
  4. Start the vacuum pump.
  5. Run the vacuum for at least 15 minutes, or until the micron gauge reads 500 microns (67 Pa).
  6. Close the low pressure side of the gauge and stop the pump.
  7. Wait 5 minutes and check that system pressure has not changed. If it changed, find and fix the leak before continuing.
  8. If pressure held, remove the cap from the high pressure (packed) valve.
  9. Insert the hex wrench into the high pressure valve and turn it 1/4 turn counterclockwise. Listen for gas to escape, then close the valve after 5 seconds.
  10. Watch the gauge for one minute. Pressure should stay steady and read slightly above atmospheric.
  11. Remove the charge hose from the service port.
  12. Open the outdoor unit stop valves fully with the hex wrench (high and low pressure valves) so refrigerant can flow.
  13. Tighten all three valve caps (service port, high pressure, low pressure) by hand, then with a torque wrench if needed.
  14. When opening valve stems, turn the hex wrench only until it hits the stopper. Do not force it further.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Air Handler codes

Models

D5FUHAH24AAKD5FUHAH36AAKD5FUHAH60AAKEHKMD05KNEHKMD08KNEHKMD10KNEHKMD15KNEHKMD20KNEHKMD25KN

More commissioning tips for air handler

Source: Carrier D5FUHA Installation Instructions, p. 61. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.