Carrier Air Conditioner: Condensate drain connection
Condensate drain connection on a Carrier air conditioner: Two 3/4 in. female threaded connections are on each coil condensate pan. Use PVC fittings and do not over-tighten.
Applies to: Condensate drain lines
How to fix condensate drain connection: step by step
- Tighten the fittings finger tight plus 1-1/2 turns.
- Install a plastic plug in the unused drain fitting.
- Pitch the condensate line 1 in. per 10 ft to an open drain or sump.
- A trap is not needed if the drain is on the supply air side of the furnace, unless local code requires one.
- If a trap is needed, install it as close to the coil as possible, at least 3 in. deep and no higher than the bottom of the drain opening.
- Make sure the trap outlet is below its connection to the pan, prime all traps, and leak test.
- Insulate traps and lines if they run above a living area.
If the unit shows an error code, look it up: Carrier Air Conditioner codes
More commissioning tips for air conditioner
Source: DLFULA Installation Instructions, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.